EV charger size by breaker and panel capacity

Short answer: Set the charger to no more than 80% of the breaker rating: 24 A on 30 A, 32 A on 40 A, 40 A on 50 A, 48 A on 60 A. NEC 625.41 requires overcurrent protection of at least 125% of the charger's load, and 625.42 treats EV charging as continuous.

Last updated:

Breaker (240 V)Max charger settingPowerMathShop
30 A24 A5.8 kW30 A ÷ 1.25 = 24 A; 24 A × 240 V = 5.8 kW—
40 A32 A7.7 kW40 A ÷ 1.25 = 32 A; 32 A × 240 V = 7.7 kW—
50 A40 A9.6 kW50 A ÷ 1.25 = 40 A; 40 A × 240 V = 9.6 kW—
60 A48 A11.5 kW60 A ÷ 1.25 = 48 A; 48 A × 240 V = 11.5 kW—
Sources: Town of Brookline, MA – Electrical Code excerpt (NEC 625.41/625.42, official PDF); ChargePoint – Electrical Design (installation guide: 32 A load needs a 40 A breaker) (accessed 2026-10-25).

Level 1 on a 120 V receptacle: max 12 A / 1.4 kVA on a 15 A receptacle, 16 A / 1.9 kVA on a 20 A receptacle (Brookline code excerpt). Source: Town of Brookline, MA – Electrical Code excerpt (NEC 625.41/625.42, official PDF) (accessed 2026-10-25).

Panel capacity

Whether a 100 A or 200 A panel can take a new 40–60 A circuit depends on a load calculation by a licensed electrician. We have no official threshold, so that part is data pending. If you do need an upgrade, national cost data:

SourceFigure
Qmerit (national)A panel upgrade adds $1,500–$3,000 to a Level 2 charger install.
HomeAdvisor (an Angi brand, national)Panel replacement $518–$2,194 (average $1,347); 200A upgrade $1,300–$2,000; 100A→200A $750–$2,000 excluding new circuits; permits and drywall add $150–$300. Page dated “Updated Jun 17, 2026”.

Panel upgrade checker · Find your plan · Federal credits

Last checked: 2026-10-25. Always follow the charger's install manual and local code. Product links appear only once a partner is set (disclosure).

What size breaker do I need for a 40 amp EV charger?

A 50 A breaker. NEC 625.41 requires overcurrent protection of at least 125% of the charger's maximum load (40 A × 1.25 = 50 A).

Can I put a 48 amp charger on a 50 A breaker?

No. 48 A × 1.25 = 60 A, so a 48 A charger needs a 60 A circuit.

Is my 100 A panel big enough?

No fixed rule: an electrician must do an NEC load calculation. We have no sourced threshold, so that is data pending.