32 A charger, hardwired on a 40 A breaker: parts list

Short answer: A 32 A charger needs a 40 A two-pole breaker, because the breaker must be at least 125% of the charger's continuous rating. 8 AWG copper covers 40 A in both the 60°C and 75°C columns of Table 310.16.

Last updated:

PartWhat to use
Circuit breaker40 A two-pole (32 A × 125% = 40 A)
Wire8 AWG copper THHN/THWN (50 A at 75°C) or 8 AWG NM-B cable (40 A at 60°C)
Conduit¾ in. is the Tesla Wall Connector's default entry; 1 in. is optional
ChargerHardwired wall unit set to 32 A (Tesla Gen 3: 40 A breaker → 32 A output)
ProtectionTesla's Wall Connector has built-in ground-fault protection; its manual says not to add a GFCI breaker

Power you get

At 240 V7.6 kW
At 208 V6.7 kW
Added in 8 hours60.8 kWh

Things to check

Ground-wire size is not listed; your electrician sizes it under NEC Table 250.122. Have a licensed electrician do the work and pull the permit. All four setups.

Sources: Mike Holt – Article 625 Electric Vehicle Power Transfer System (PDF); NEC Table 310.16 ampacities (nectables.com restatement); Tesla – Gen 3 Wall Connector installation manual (PDF) (accessed 2026-10-25).