Short answer: The breaker must be at least 125% of the charger's continuous current (NEC 625.41), and the wire must carry that breaker's rating under NEC Table 310.16. Pick your setup below for the exact breaker, wire, outlet and conduit.

Last updated:

SetupCharger drawsBreakerPower at 240 VAt 208 VAdded in 8 hours
Level 1, 120 V12 A or 16 A15 A or 20 A1.3 kW (5-15) / 1.7 kW (5-20)n/a (120 V)10.4 kWh / 13.6 kWh
32 A hardwired32 A40 A two-pole7.6 kW6.7 kW60.8 kWh
40 A plug-in, 14-5040 A50 A two-pole9.6 kW8.3 kW76.8 kWh
48 A hardwired48 A60 A two-pole11.5 kW10.0 kW92 kWh

Copper wire ampacity used on these pages

Copper size60°C (NM-B cable)75°C (THHN/THWN)90°C
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A

14, 12 and 10 AWG are capped at 15 A, 20 A and 30 A of overcurrent protection by NEC 240.4(D). NM-B cable must use the 60°C column (NEC 334.80). Any EV charger above 16 A or 120 V needs its own branch circuit (NEC 625.40).

What these lists leave out

We don't list ground-wire sizes. Your electrician sizes the equipment ground from NEC Table 250.122 and local amendments. We also don't list brands or prices, and the links are plain links with no affiliate tags.

Have a licensed electrician check your panel, pull the permit and do the work. Local code can be stricter than the NEC edition cited here.

Sources: NEC Table 310.16 ampacities (nectables.com restatement); Mike Holt – Article 625 Electric Vehicle Power Transfer System (PDF); Mike Holt newsletter – 625.40 individual branch circuit; City of Saint Paul – 2023 NEC garage electrical checklist (PDF); Tesla – Gen 3 Wall Connector installation manual (PDF); ChargePoint – Home Flex: wire the circuit (accessed 2026-10-25).