40 A charger on a NEMA 14-50 outlet (50 A breaker): parts list

Short answer: A plug-in charger drawing 40 A needs a 50 A circuit and a NEMA 14-50 or 6-50 outlet. Mike Holt's Article 625 guide pairs that 50 A breaker with 8 AWG copper rated 75°C, or 6 AWG if you use NM cable.

Last updated:

PartWhat to use
Circuit breaker50 A two-pole (40 A × 125% = 50 A)
Wire8 AWG copper THHN/THWN at 75°C (50 A), or 6 AWG NM-B cable (55 A at 60°C)
OutletNEMA 14-50R or 6-50R; ChargePoint asks for the outlet 20–26 in. off the floor because its input cord is 12 in.
ChargerPlug-in unit set to 40 A (ChargePoint Home Flex: 50 A circuit → 40 A max)
ProtectionThe 2023 NEC requires GFCI on this garage outlet; ChargePoint recommends hardwiring where GFCI is required, to avoid nuisance trips

Power you get

At 240 V9.6 kW
At 208 V8.3 kW
Added in 8 hours76.8 kWh

Things to check

Ground-wire size is not listed; your electrician sizes it under NEC Table 250.122. Have a licensed electrician do the work and pull the permit. All four setups.

Sources: Mike Holt – Article 625 Electric Vehicle Power Transfer System (PDF); NEC Table 310.16 ampacities (nectables.com restatement); ChargePoint – Home Flex electrician installation tips; ChargePoint – Home Flex: wire the circuit; City of Saint Paul – 2023 NEC garage electrical checklist (PDF) (accessed 2026-10-25).