48 A charger, hardwired on a 60 A breaker: parts list

Short answer: A 48 A charger needs a 60 A breaker, not 40 A: 48 A × 125% = 60 A. It must be hardwired. Tesla's manual calls for 6 AWG copper rated 90°C with a 75°C breaker, or 4 AWG if the breaker is rated 60°C.

Last updated:

PartWhat to use
Circuit breaker60 A two-pole (48 A × 125% = 60 A)
Wire6 AWG copper (65 A at 75°C) with a 75°C-rated breaker; 4 AWG with a 60°C breaker or NM-B cable (70 A at 60°C)
Conduit¾ in. default, 1 in. optional on the Tesla Gen 3; ChargePoint uses a ¾ in. knockout
ChargerHardwired only (Tesla Gen 3: 60 A → 48 A, 11.5 kW; ChargePoint Home Flex: 60 A → 48 A)
Terminal limitTesla accepts 12–4 AWG copper; ChargePoint's field terminal takes 6 AWG at most (rated 105°C, use 90°C copper wire)

Power you get

At 240 V11.5 kW
At 208 V10.0 kW
Added in 8 hours92 kWh

Things to check

Ground-wire size is not listed; your electrician sizes it under NEC Table 250.122. Have a licensed electrician do the work and pull the permit. All four setups.

Sources: Mike Holt – Article 625 Electric Vehicle Power Transfer System (PDF); NEC Table 310.16 ampacities (nectables.com restatement); Tesla – Gen 3 Wall Connector installation manual (PDF); ChargePoint – Home Flex: wire the circuit (accessed 2026-10-25).